The BTU Meter reads the consumption of the chilled water service in BTUs and converted into Ton.hrs .
Consumption = K (constant) x Flow x ( T2-T1) .
In this case as shown in the figure , T1 = 5 C , T2 = 13 , so ∆T(T2-T1)= 9 C
The readings are taken from District Cooling Side
If the BTU meter is connected with T3 instead of T2 ( which is Customer CWRT ) ; This practice yield extra charges as following , assuming the temperatures were as per the figure . 1- Consumption Charges : Meter Consumption Reading : K x Flow x ( 16-5) =K x Flow x 11 Difference + ( K x Flow x 11)/( K x Flow x 9)=11/9 =22.2%. So , the metered consumption is 22.2% more than actual consumption . 2- Capacity Charges : The Contracted Capacity is being compared with the BTU meter reading . The reading values during the peak hours of the Building are recorded and averaged for few hours and compared with the Contracted Capacity. With such wiring connection , the BTU meter will read that the measured (metered ) Capacity is 22.2% more than the actual peak ; and therefore . should be avoided from being practiced.
It would be much more beneficial if another BTU Meter is installed on the Customer Side.
Each BTU Meter will read it sown side .
Q1 (Cooling Delivered by DCP)= Q2 ( Heat Rejected by the Customer + Q3(Cooling Loss)
The Cooling Loss is normally neglected !
Adding a second BTU Meter on the Customer Side will create a data bank of the Customer Building which some of them are :
- Flow of Chilled water rates on timely basis around the years .
- Chilled Water Supply Temp (CWST) , and Chilled water Return Temp (CWRT)
- Actual Delta T across the ETS on Customer side
- Approach Temp which is an important factor to determine the proper size of the ETS.
- The Cooling Loss ( Q3) , since it will make it possible now to compare both Q1 and Q2
- Building Heat Rate Data around the year ( kW/Sq. ft ) or Sq.ft/Ton
- By comparing the Q2 with the individual BTU meters of each apartment/office/.. an idea of how much losses are there in the general hydronic system of the Building .
- If the total values of the individual BTU meters are more than Q2 , this will alarm that :
Either some of the individual meters are not reading properly or the BTU Meter #2 itself is a faulty .
We use cookies to analyze website traffic and optimize your website experience. By accepting our use of cookies, your data will be aggregated with all other user data.